Technical Data
KG125
Thermal Current: lu/lth [A]: 125
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 45 / AC-3 [kW]: 37
KG160
Thermal Current: lu/lth [A]: 160
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 55 / AC-3 [kW]: 45
KG210
Thermal Current: lu/lth [A]: 200
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 75 / AC-3 [kW]: 55
KG250
Thermal Current: lu/lth [A]: 250
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 90 / AC-3 [kW]: 55
KG315
Thermal Current: lu/lth [A]: 315
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 110 / AC-3 [kW]: 75
C316
Thermal Current: lu/lth [A]: 315
Utilization Category (3 x 380 V – 440 V): AC-23A [kW]: 132 / AC-3 [kW]: 55
Switching Function:
- ON/OFF-Switches
2, 3, 4, 6 and 8 pole