KRAUS & NAIMER CL4 - Electrical Data 1.12.2006

Switch features:
- S00 (30x30mm) Front element size (can be changed by mountings and optional extras)
- Designed for vertical wiring (resp. horizontal for -V mountings: e.g. VE-V, FS1-V)
- Finger-proof terminals (IP20)
- Contacts with 1µm gold plating
- Insulation Displacement Connection (IDC); No insulation stripping or preparation of the conductor is required

Approvals:

Approved Confirms to requirements No listing required
BS EN, CH, D, FI, IEC, N, ÖVE, S, VDE

BS EN...BS EN 60947 - British Standards Institution, CCC...CCC - China Compulsory Certification, CH...Schweizerischer Elektrotechnischer Verein, CSA...Canadian Standards Association, CUL...Canadian National Standards - Listed, CULUS...Canadian National and United States Standards - Listed, CUR...Canadian National Standards - Recognized, CURUS...Canadian National and United States Standards - Recognized, D...Danmarks Elektriske Materiellkontrol, FI...Sähkötarkastuskeskus, GOST...GOST - gosudarstvennyj standard, IEC...IEC 60947 - International Electrical Commission (IEC) Recommendation, N...Norges Elektriske Materiellkontroll, ÖVE...Österreichischer Verband für Elektrotechnik, RuMRS...Russian Maritime Register of Shipping, S...Svenska Elektriska Materielkontrollanstalten, UL...United States Standards - Listed, UR...United States Standards - Recognized, VDE...VDE 0660 - Verband Deutscher Elektrotechniker

Note the remarks in the approval table!: here or at http://www.krausnaimer.com/0/apps.htm

AC-Values:

IEC 60947-3, EN 60947-3, VDE 0660 part 107:
Rated Operational Voltage Ue440V 1)
Rated Insulation Voltage Ui440V 1)
Rated Thermal Current Iu/Ith10A 2)
Breaking Capacity
220V-240V:   
50A 2)
380V-440V:   
50A 2)
Rated Operational Current Ie
AC-15 Switching of control devices, contactors, valves etc.
220V-240V:   
2.5A 2)
380V-440V:   
1.5A 2)
AC-21A Switching of resistive loads, including moderate overloads
For switching of power >1kW 10A 2)
AC-22A Switching of combined resistive or low inductive loads including moderate overloads
220V-500V:   
10A 2)
Rated Utilization Category
AC-2 Slip ring motor starting, reversing and plugging, star-delta starting 3 phase, 3 pole
220V-240V:   
2.5kW 2)
380V-440V:   
4.5kW 2)
AC-3 Direct-on-line starting, star-delta starting
3 phase, 3 pole
220V-240V:   
1.5kW 2)
380V-440V:   
2.2kW 2)
1 phase, 2 pole
110V-120V:   
0.3kW 2)
220V-240V:   
0.55kW 2)
380V-440V:   
0.75kW 2)
AC-4 Direct-on-line starting, reversing, plugging and inching
3 phase, 3 pole
220V-240V:   
0.37kW 2)
380V-440V:   
0.55kW 2)
1 phase, 2 pole
110V-120V:   
0.15kW 2)
220V-240V:   
0.25kW 2)
380V-440V:   
0.5kW 2)
AC-23A Frequent switching of motors or other high inductive loads
3 phase, 3 pole
220V-240V:   
1.8kW 2)
380V-440V:   
3kW 2)
1 phase, 2 pole
110V-120V:   
0.37kW 2)
220V-240V:   
0.75kW 2)
380V-440V:   
1.1kW 2)
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category III, Other values on request.
2)...IEC 60947-3, EN 60947-3, VDE 0660 part 107

DC-Values:

Resistive loads (T<=1ms)
Number of series contact(s) DC-switching capacity
1 2 3 4 5 6 8
440V 660V 0.2A
220V 440V 660V 0.3A
110V 220V 330V 440V 550V 660V 0.7A
24V 48V 70V 95V 120V 145V 190V 10A
60V 120V 180V 240V 300V 360V 450V 2.5A
48V 95V 140V 190V 240V 290V 350V 6A

Inductive load (T=50ms)
Number of series contact(s) DC-switching capacity
1 2 3 4 5 6 8
110V 220V 330V 440V 550V 660V 0.3A
60V 120V 180V 240V 300V 360V 450V 0.7A
48V 95V 140V 190V 240V 290V 350V 1A
30V 60V 90V 120V 150V 180V 240V 3A
24V 48V 70V 95V 120V 145V 190V 6A

General:

Minimum Voltage on request
Power loss per contact at Iu0.4W
Resistance to vibration min. 4g, 2-100Hz, 1.6mm
Resistance to shock min. 5g, 6ms
Rated Impulse Withstand Voltage Uimp4kV 1)
Short Circuit Protection
Max. fuse size (gL/gG-characteristic)10A
Rated short-time withstand current (1s-current)90A
Ambient Temperature of Stages (for switches with electro-mechanical accessories refer to optional extra)
open at 100% Iu/Ith 55°C during 24 hours with peaks up to 60°C
enclosed at 100% Ithe 35°C during 24 hours with peaks up to 40°C
Storage temperature -40°C to 85°C (in case of temperature below -5°C no shock load permissible)
Permissible connecting ambiente temperature range5-40°C
Terminal lead material copper wires only
Max. Permissible Wire Gage
Single-core or stranded wire1x0.5-1.5mm2
Flexible wire1x0.5-1.5mm2
Connecting wire - outside diameter1.5-2.8mm
Connecting wire - plug-in depth8.5mm
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category III, Other values on request.

Additional information:
The insulation material of the conductor has to be PVC (typical wire codes H05V-K0,5 ... H07V-K1,5 or H05V-U0,5 ... H07V-U1,5 etc.). Other materials have to be approved. Please contact our sales office for this. Connected conductors, which have to be disconnected and re-connected again must be cut in order to ensure a proper electrical connection and to prevent a complete cut-off of the wire insulation. The permissible ambient temperature range when connecting the wires is 5-40 deg.C