KRAUS & NAIMER CGD4-1 - Electrical Data 20.2.2008

Switch features:
- S00 (30x30mm) Front element size (can be changed by mountings and optional extras)
- Terminal screws accessible from the installation view
- Designed for horizontal wiring (resp. vertical for -V mountings: e.g. VE-V, FS1-V)
- Installable without spacing to other devices in vertical direction (resp. horizontal for -V mountings )
- H-brige for high contact reliability at lower voltages
- Finger-proof terminals (IP20)
- Contacts with 35µm gold plating

Approvals:

Approved Confirms to requirements No listing required
CUL, CULUS, UL BS EN, CH, D, FI, GOST, IEC, N, ÖVE, S, VDE

BS EN...BS EN 60947 - British Standards Institution, CCC...CCC - China Compulsory Certification, CH...Schweizerischer Elektrotechnischer Verein, CSA...Canadian Standards Association, CUL...Canadian National Standards - Listed, CULUS...Canadian National and United States Standards - Listed, CUR...Canadian National Standards - Recognized, CURUS...Canadian National and United States Standards - Recognized, D...Danmarks Elektriske Materiellkontrol, FI...Sähkötarkastuskeskus, GOST...GOST - gosudarstvennyj standard, IEC...IEC 60947 - International Electrical Commission (IEC) Recommendation, N...Norges Elektriske Materiellkontroll, ÖVE...Österreichischer Verband für Elektrotechnik, RuMRS...Russian Maritime Register of Shipping, S...Svenska Elektriska Materielkontrollanstalten, UL...United States Standards - Listed, UR...United States Standards - Recognized, VDE...VDE 0660 - Verband Deutscher Elektrotechniker

Note the remarks in the approval table!: here or at http://www.krausnaimer.com/0/apps.htm

AC-Values:

IEC 60947-3, EN 60947-3, VDE 0660 part 107:
Rated Operational Voltage Ue440V 1)
Rated Insulation Voltage Ui440V 1)
Rated Thermal Current Iu/Ith5A 2)
Rated Operational Current Ie
AC-21A Switching of resistive loads, including moderate overloads
For switching of power <1kW 1V5A 2)
For switching of power <1kW 6V2A 2)
For switching of power <1kW 12V1.2A 2)
For switching of power <1kW 24 V0.7A 2)
For switching of power <1kW 48V0.45A 2)
For switching of power <1kW 110V0.25A 2)
For switching of power <1kW 240V0.15A 2)
For switching of power <1kW 300V0.13A 2)
For switching of power <1kW 440V0.1A 2)
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category III, Other values on request.
2)...IEC 60947-3, EN 60947-3, VDE 0660 part 107

UL/Canada:
Rated Voltage300V 1)
Rated Insulation Voltage Ui300V 1)
Rated Thermal Current5A 1)
Rated Operational Current Ie
AC-21A Switching of resistive loads, including moderate overloads
For switching of power <1kW 1V5A 1)
For switching of power <1kW 6V2A 1)
For switching of power <1kW 12V1.2A 1)
For switching of power <1kW 24 V0.7A 1)
For switching of power <1kW 48V0.45A 1)
For switching of power <1kW 110V0.25A 1)
For switching of power <1kW 240V0.15A 1)
For switching of power <1kW 300V0.13A 1)
1)...UL/Canada - Refer to International Standards and Approvals

DC-Values:

Resistive loads (T<=1ms)
Number of series contact(s) DC-switching capacity
1 2 3 4 5 6 8
440V 0.05A
300V 0.07A
240V 0.08A
110V 0.13A
60V 0.2A
48V 0.25A
24V 0.4A
12V 0.7A
6V 1.2A
1V 3A


General:

Minimum Voltage on request
Rated Impulse Withstand Voltage Uimp on request1)
Short Circuit Protection
Max. fuse size (G-fuse, quick)5A
Rated short-time withstand current (1s-current)30A
Ambient Temperature of Stages (for switches with electro-mechanical accessories refer to optional extra)
open at 100% Iu/Ith 55°C during 24 hours with peaks up to 60°C
enclosed at 100% Ithe 35°C during 24 hours with peaks up to 40°C
Storage temperature -40°C to 85°C (in case of temperature below -5°C no shock load permissible)
Terminal lead material copper wires only
Max. Permissible Wire Gage
Single-core or stranded wire2x1.5mm2
2xAWG 14
Flexible wire2x1.5mm2
2xAWG 16
Flexible wire with sleeving in accordance with DIN 462282x1mm2
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category III, Other values on request.