KRAUS & NAIMER CAD12R - Electrical Data 1.12.2006

Switch features:
- S0 (48x48mm) Front element size (can be changed by mountings and optional extras)
- Terminal screws accessible laterally (resp. from above and below for -V mountings)
- Designed for vertical wiring (resp. horizontal for -V mountings: e.g. VE-V, FS1-V)
- H-brige for high contact reliability at lower voltages
- Finger-proof terminals (IP20)

Approvals:

Approved Confirms to requirements No listing required
CUL, CULUS, UL BS EN, CH, D, FI, IEC, N, ÖVE, S, VDE

BS EN...BS EN 60947 - British Standards Institution, CCC...CCC - China Compulsory Certification, CH...Schweizerischer Elektrotechnischer Verein, CSA...Canadian Standards Association, CUL...Canadian National Standards - Listed, CULUS...Canadian National and United States Standards - Listed, CUR...Canadian National Standards - Recognized, CURUS...Canadian National and United States Standards - Recognized, D...Danmarks Elektriske Materiellkontrol, FI...Sähkötarkastuskeskus, GOST...GOST - gosudarstvennyj standard, IEC...IEC 60947 - International Electrical Commission (IEC) Recommendation, N...Norges Elektriske Materiellkontroll, ÖVE...Österreichischer Verband für Elektrotechnik, RuMRS...Russian Maritime Register of Shipping, S...Svenska Elektriska Materielkontrollanstalten, UL...United States Standards - Listed, UR...United States Standards - Recognized, VDE...VDE 0660 - Verband Deutscher Elektrotechniker

Note the remarks in the approval table!: here or at http://www.krausnaimer.com/0/apps.htm

AC-Values:

IEC 60947-3, EN 60947-3, VDE 0660 part 107:
Rated Operational Voltage Ue600V 1)
Rated Insulation Voltage Ui600V 1)
Rated Thermal Current Iu/Ith6A 2)
Rated Operational Current Ie
AC-20A No-load operation6A 2)
AC-21A Switching of resistive loads, including moderate overloads
For switching of power <1kW 6V6A 2)
For switching of power <1kW 12V5A 2)
For switching of power <1kW 24 V5A 2)
For switching of power <1kW 48V4A 2)
For switching of power <1kW 110V3A 2)
For switching of power <1kW 220V2A 2)
For switching of power <1kW 400V1.3A 2)
For switching of power <1kW 440V1A 2)
For switching of power <1kW 500V0.8A 2)
For switching of power <1kW 600V0.5A 2)
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category III, Other values on request.
2)...IEC 60947-3, EN 60947-3, VDE 0660 part 107

UL/Canada:
Rated Voltage300V 1)
Rated Insulation Voltage Ui300V 1)
Rated Thermal Current6A 1)
Rated Operational Current Ie
AC-21A Switching of resistive loads, including moderate overloads
For switching of power <1kW 6V6A 1)
For switching of power <1kW 12V5A 1)
For switching of power <1kW 24 V5A 1)
For switching of power <1kW 48V4A 1)
For switching of power <1kW 110V3A 1)
For switching of power <1kW 220V2A 1)
1)...UL/Canada - Refer to International Standards and Approvals

DC-Values:

Resistive loads (T<=1ms)
Number of series contact(s) DC-switching capacity
1 2 3 4 5 6 8
600V 0.1A
500V 0.1A
240V 0.25A
220V 0.3A
110V 0.6A
60V 1A
48V 1.2A
24V 2.2A
12V 3A
6V 4A


General:

Minimum Voltage on request
Power loss per contact at Iu0.2W
Rated Impulse Withstand Voltage Uimp on request1)
Short Circuit Protection
Max. fuse size (gL/gG-characteristic)6A
Rated short-time withstand current (1s-current)50A
Ambient Temperature of Stages (for switches with electro-mechanical accessories refer to optional extra)
open at 100% Iu/Ith 55°C during 24 hours with peaks up to 60°C
enclosed at 100% Ithe 35°C during 24 hours with peaks up to 40°C
Storage temperature -40°C to 85°C (in case of temperature below -5°C no shock load permissible)
Terminal lead material copper wires only
Max. Permissible Wire Gage
Single-core or stranded wire2x2.5mm2
2xAWG 12
Flexible wire2x2.5mm2
2xAWG 14
Flexible wire with sleeving in accordance with DIN 462282x2.5mm2
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category III, Other values on request.