| KRAUS & NAIMER |
C315 - Electrical Data |
1.12.2006 |
Switch features:
- S3 (130x130mm) Front element size (can be changed by mountings and optional extras)
- Terminal screws accessible laterally (resp. from above and below for -V mountings)
- Designed for horizontal wiring (resp. vertical for -V mountings: e.g. VE-V, FS1-V)
Approvals:
| Approved |
Confirms to requirements |
No listing required |
| CSA, CUR, CURUS, GOST, UR |
BS EN, CH, IEC, VDE |
D, FI, N, ÖVE, S |
BS EN...BS EN 60947 - British Standards Institution, CCC...CCC - China Compulsory Certification, CH...Schweizerischer Elektrotechnischer Verein, CSA...Canadian Standards Association, CUL...Canadian National Standards - Listed, CULUS...Canadian National and United States Standards - Listed, CUR...Canadian National Standards - Recognized, CURUS...Canadian National and United States Standards - Recognized, D...Danmarks Elektriske Materiellkontrol, FI...Sähkötarkastuskeskus, GOST...GOST - gosudarstvennyj standard, IEC...IEC 60947 - International Electrical Commission (IEC) Recommendation, N...Norges Elektriske Materiellkontroll, ÖVE...Österreichischer Verband für Elektrotechnik, RuMRS...Russian Maritime Register of Shipping, S...Svenska Elektriska Materielkontrollanstalten, UL...United States Standards - Listed, UR...United States Standards - Recognized, VDE...VDE 0660 - Verband Deutscher Elektrotechniker
AC-Values:
IEC 60947-3, EN 60947-3, VDE 0660 part 107:
| Rated Operational Voltage Ue | | 690V | 1) |
| Rated Insulation Voltage Ui | | 690V | 1) |
| Rated Thermal Current Iu/Ith | | 315A | 2) |
| Breaking Capacity |
220V-240V:
| 2000A | 2) |
|
|
|
380V-440V:
| 2000A | 2) |
|
|
|
660V-690V:
| 335A | 2) |
| Rated Operational Current Ie |
| AC-20A No-load operation | | 315A | 2) |
| AC-21A Switching of resistive loads, including moderate overloads |
|
|
For switching of power >1kW | | 315A | 2) |
| AC-22A Switching of combined resistive or low inductive loads including moderate overloads |
220V-500V:
| 315A | 2) |
|
|
|
660V-690V:
| 125A | 2) |
| Rated Utilization Category |
| AC-2 Slip ring motor starting, reversing and plugging, star-delta starting 3 phase, 3 pole |
220V-240V:
| 55kW | 2) |
|
|
|
380V-440V:
| 90kW | 2) |
|
|
|
500V-500V:
| 110kW | 2) |
|
|
|
660V-690V:
| 55kW | 2) |
| AC-3 Direct-on-line starting, star-delta starting |
|
|
3 phase, 3 pole |
220V-240V:
| 37kW | 2) |
|
|
|
380V-440V:
| 55kW | 2) |
|
|
|
500V-500V:
| 55kW | 2) |
|
|
|
660V-690V:
| 37kW | 2) |
|
|
1 phase, 2 pole |
110V-120V:
| 11kW | 2) |
|
|
|
220V-240V:
| 22kW | 2) |
|
|
|
380V-440V:
| 30kW | 2) |
| AC-4 Direct-on-line starting, reversing, plugging and inching |
|
|
3 phase, 3 pole |
220V-240V:
| 15kW | 2) |
|
|
|
380V-440V:
| 25kW | 2) |
|
|
|
500V-500V:
| 25kW | 2) |
|
|
|
660V-690V:
| 22kW | 2) |
|
|
1 phase, 2 pole |
110V-120V:
| 4kW | 2) |
|
|
|
220V-240V:
| 7.5kW | 2) |
|
|
|
380V-440V:
| 11kW | 2) |
| AC-23A Frequent switching of motors or other high inductive loads |
|
|
3 phase, 3 pole |
220V-240V:
| 75kW | 2) |
|
|
|
380V-440V:
| 132kW | 2) |
|
|
|
500V-500V:
| 132kW | 2) |
|
|
|
660V-690V:
| 37kW | 2) |
|
|
1 phase, 2 pole |
110V-120V:
| 18.5kW | 2) |
|
|
|
220V-240V:
| 37kW | 2) |
|
|
|
380V-440V:
| 55kW | 2) |
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category
III, Other values on request.
2)...IEC 60947-3, EN 60947-3, VDE 0660 part 107
UL/Canada:
| Rated Voltage | | 600V | 1) |
| Rated Insulation Voltage Ui | | 600V | 1) |
| Rated Thermal Current | | 240A | 1) |
| Ampere Rating - Resistive or low inductive loads |
| For switching of power >1kW | | 240A | 1) |
| Ratings |
| Standard motor load, DOL Rating (similar AC-3) |
|
|
3 phase, 3 pole |
110V-120V:
| 30HP | 2) |
|
|
|
220V-240V:
| 75HP | 2) |
|
|
|
440V-480V:
| 75HP | 2) |
|
|
|
550V-600V:
| 60HP | 2) |
|
|
1 phase, 2 pole |
110V-120V:
| 15HP | 2) |
|
|
|
220V-240V:
| 40HP | 2) |
|
|
|
277V-277V:
| 40HP | 2) |
|
|
|
440V-480V:
| 50HP | 2) |
|
|
|
550V-600V:
| 50HP | 2) |
| Heavy motor Load-reversing (similar AC-4) |
|
|
3 phase, 3 pole |
110V-120V:
| 15HP | 2) |
|
|
|
220V-240V:
| 30HP | 2) |
|
|
|
440V-600V:
| 40HP | 2) |
|
|
1 phase, 2 pole |
110V-120V:
| 7.5HP | 2) |
|
|
|
220V-240V:
| 15HP | 2) |
|
|
|
277V-277V:
| 15HP | 2) |
| Pilot Duty, Heavy | | A600 | 1) |
1)...UL/Canada - Refer to International Standards and Approvals
2)...UL/Canada
DC-Values:
Resistive loads (T<=1ms)
DC switching capacity applies to ON/OFF switches. Switching capacity for other configurations on request.
| Number of series contact(s) |
DC-switching capacity |
| 1 |
2 |
3 |
4 |
5 |
6 |
8 |
| 48V
|
95V
|
140V
|
190V
|
240V
|
290V
|
350V
|
250A |
| 24V
|
48V
|
70V
|
95V
|
120V
|
145V
|
190V
|
315A |
Inductive load (T=50ms)
DC switching capacity applies to ON/OFF switches. Switching capacity for other configurations on request.
| Number of series contact(s) |
DC-switching capacity |
| 1 |
2 |
3 |
4 |
5 |
6 |
8 |
| 24V
|
48V
|
70V
|
95V
|
120V
|
145V
|
190V
|
250A |
| 30V
|
60V
|
90V
|
120V
|
150V
|
180V
|
240V
|
70A |
General:
| Minimum Voltage | | on request | |
| Power loss per contact at Iu | | 17W | |
| Resistance to vibration | | on request | |
| Resistance to shock | | min. 5g, 30ms | |
| Rated Impulse Withstand Voltage Uimp | | 6kV | 1) |
| Short Circuit Protection |
| Max. fuse size (gL/gG-characteristic) | | 315A | |
| Rated short-time withstand current (1s-current) | | 4200A | |
| Ambient Temperature of Stages (for switches with electro-mechanical accessories refer to optional extra) |
| open at 100% Iu/Ith | | 55°C during 24 hours with peaks up to 60°C | |
| enclosed at 100% Ithe | | 35°C during 24 hours with peaks up to 40°C | |
| Storage temperature | | -40°C to 85°C (in case of temperature below -5°C no shock load permissible) | |
| Terminal lead material | | copper wires only | |
| Max. Permissible Wire Gage |
| Single-core or stranded wire | | 185mm2 Cable lug must accept M12 screw. | |
|
| | MCM 350 | |
| Flexible wire | | 150mm2 Cable lug must accept M12 screw. | |
|
| | MCM 300 | |
1)...IEC 60947-3, EN 60947-3, VDE 0660 part 107 - Valid for lines with grounded common neutral termination, overvoltage category
III, Other values on request.