COIL CHARACTERISTICS - TYPE R35../R36..

Voltage Range:
AC 50 Hz
24 V - 550 V
AC 60 Hz
24 V - 600 V
DC
24 V - 240 V

Coil Power Consumption at 100 % Uc:
 
Pull in
Seal in
AC 50 Hz
140 VA
14 VA / 3.5 W
AC 60 Hz
170 VA
18 VA / 4 W
DC (incl. economy resistor)
200 W
17.5 W

Operational Limits:
 
Pull in
Drop out
AC powered 50-60 Hz
min. 0.75 - 0.85 Uc / max. 1.1 Uc
0.4 Uc - 0.6 Uc
DC powered
min. 0.7 - 0.8 Uc / max. 1.1 Uc
0.2 - 0.5 Uc

General:
 
Pull in
Drop out
Response Time at 100 % Uc
12 ms- 22 ms
8 ms - 16 ms

Main Contact Bounce at 100 % Uc:
max. 4 ms
Max. Permissible Ambient Temperature:
 
Open
55°C during 24 hours with peaks up to 60°C
Enclosed
35°C during 24 hours with peaks up to 40°C

Contact Life: Permissible Number of Operations
Click here for printable version (PDF-File)