COIL CHARACTERISTICS - TYPE R26../R27..

Voltage Range:
AC 50 Hz
24 V - 550 V
AC 60 Hz
24 V - 600 V
DC
24 V - 240 V

Coil Power Consumption at 100 % Uc:
 
Pull in
Seal in
AC 50 Hz
60 VA
10 VA / 3 W
AC 60 Hz
75 VA
12 VA / 4 W
DC (incl. economy resistor)
100 W
14 W

Operational Limits:
 
Pull in
Drop out
AC powered 50-60 Hz
min. 0.75 - 0.85 Uc / max. 1.1 Uc
0.4 Uc - 0.6 Uc
DC powered
min. 0.7 - 0.8 Uc / max. 1.1 Uc
0.2 - 0.5 Uc

General:
 
Pull in
Drop out
Response Time at 100 % Uc
14 ms- 25 ms
8 ms - 22 ms

Main Contact Bounce at 100 % Uc:
max. 5 ms
Max. Permissible Ambient Temperature:
 
Open
55°C during 24 hours with peaks up to 60°C
Enclosed
35°C during 24 hours with peaks up to 40°C

Contact Life: Permissible Number of Operations for Type R26..
Click here for printable version (PDF-File)

Contact Life: Permissible Number of Operations for Type R27..
Click here for printable version (PDF-File)