COIL CHARACTERISTICS - TYPE S15../S17..

Voltage Range:
AC 50 Hz
24 V - 550 V
AC 60 Hz
24 V - 600 V
DC
24 V - 240 V

Coil Power Consumption at 100 % Uc:
 
Pull in
Seal in
AC 50 Hz
55 VA
8 VA / 2.5 W
AC 60 Hz
70 VA
10 VA / 3.3 W
DC (incl. economy resistor)
100 W
11 W

Operational Limits:
 
Pull in
Drop out
AC powered 50-60 Hz
min. 0.75 - 0.85 Uc / max. 1.1 Uc
0.4 Uc - 0.6 Uc
DC powered
min. 0.7 - 0.8 Uc / max. 1.1 Uc
0.2 - 0.5 Uc

General:
 
Pull in
Drop out
Response Time at 100 % Uc
9 ms- 16 ms
6 ms - 17 ms

Main Contact Bounce at 100 % Uc:
max. 4 ms
Max. Permissible Ambient Temperature:
 
Open
55°C during 24 hours with peaks up to 60°C
Enclosed
35°C during 24 hours with peaks up to 40°C

Contact Life: Permissible Number of Operations