Voltage Range:
AC 50 Hz | 24 V - 550 V |
AC 60 Hz | 24 V - 600 V |
DC | 24 V - 240 V |
Coil Power Consumption at 100 % Uc:
| | Pull in | Seal in |
AC 50 Hz | 55 VA | 8 VA / 2.5 W |
AC 60 Hz | 70 VA | 10 VA / 3.3 W |
DC (incl. economy resistor) | 100 W | 11 W |
Operational Limits:
| | Pull in | Drop out |
AC powered 50-60 Hz | min. 0.75 - 0.85 Uc / max. 1.1 Uc | 0.4 Uc - 0.6 Uc |
DC powered | min. 0.7 - 0.8 Uc / max. 1.1 Uc | 0.2 - 0.5 Uc |
General:
| | Pull in | Drop out |
Response Time at 100 % Uc | 7 ms- 13 ms | 6 ms - 17 ms |
|
Main Contact Bounce at 100 % Uc: | max. 4 ms |
|
Max. Permissible Ambient Temperature: | |
| Open | 55°C during 24 hours with peaks up to 60°C |
| Enclosed | 35°C during 24 hours with peaks up to 40°C |
|
Contact Life: Permissible Number of Operations
DC-Control:
Contactors may be DC controlled if economy resistors are used. Contactors for DC are equipped with a delayed auxiliary contact. |
Contactor | Terminal markings for delayed auxiliary contacts |  |
X | Y |
S1000, S1200 | 21 | 22 |
S1010, S1210 | 21 | 22 |
S1002, S1202 | 21 | 22 |
S1020 | 11 | 12 |
|
Details of required Economy Resistor:
|
Required Operational Voltage DC Uc in [V] | Resistance R in [W] |
Power in [W] |
24 | 56 | 10 |
28 | 82 | 10 |
30 | 82 | 10 |
32 | 100 | 10 |
36 | 120 | 10 |
40 | 180 | 10 |
42 | 180 | 10 |
48-50 | 270 | 10 |
60 | 390 | 10 |
74 | 560 | 10 |
95-100 | 1000 | 10 |
105 | 1200 | 10 |
110-115 | 1200 | 10 |
120-125 | 1500 | 10 |
130-140 | 1800 | 10 |
180 | 3900 | 10 |
200 | 3900 | 10 |
220 | 4700 | 10 |
240 | 5600 | 10 |
|
Minimum Command Trigger Circuit for Impulse Energizing:
 |
* Pull in
** Drop out
*** without drop out |
|
Commands for pull in and drop out require the following minimum duration in ms:
|
Pull in a | Drop out b |
Max. duration of triggering without drop out c |
25-30 | 25-30 | 8 VA / 2.5 W |
|
Change-over Time:
De-energizing of contactor A causes energizing of contactor B (control switch).
* Signal TA ** main contacts A *** main contacts B |
|
Commands for pull in and drop out require the following minimum duration in ms:
|
Response time in ms |
a | b |
20-30 | 10-17 |
|
|