COIL CHARACTERISTICS - TYPE S10../S12..

Voltage Range:
AC 50 Hz
24 V - 550 V
AC 60 Hz
24 V - 600 V
DC
24 V - 240 V

Coil Power Consumption at 100 % Uc:
 
Pull in
Seal in
AC 50 Hz
55 VA
8 VA / 2.5 W
AC 60 Hz
70 VA
10 VA / 3.3 W
DC (incl. economy resistor)
100 W
11 W

Operational Limits:
 
Pull in
Drop out
AC powered 50-60 Hz
min. 0.75 - 0.85 Uc / max. 1.1 Uc
0.4 Uc - 0.6 Uc
DC powered
min. 0.7 - 0.8 Uc / max. 1.1 Uc
0.2 - 0.5 Uc

General:
 
Pull in
Drop out
Response Time at 100 % Uc
7 ms- 13 ms
6 ms - 17 ms

Main Contact Bounce at 100 % Uc:
max. 4 ms
Max. Permissible Ambient Temperature:
 
Open
55°C during 24 hours with peaks up to 60°C
Enclosed
35°C during 24 hours with peaks up to 40°C

Contact Life: Permissible Number of Operations
Click here for printable version (PDF-File)

DC-Control:
Contactors may be DC controlled if economy resistors are used. Contactors for DC are equipped with a delayed auxiliary contact.
Contactor
Terminal markings for delayed auxiliary contacts
X
Y
S1000, S1200
21
22
S1010, S1210
21
22
S1002, S1202
21
22
S1020
11
12

Details of required Economy Resistor:
Required Operational Voltage
DC Uc in [V]
Resistance
R in [W]
Power
in [W]
24
56
10
28
82
10
30
82
10
32
100
10
36
120
10
40
180
10
42
180
10
48-50
270
10
60
390
10
74
560
10
95-100
1000
10
105
1200
10
110-115
1200
10
120-125
1500
10
130-140
1800
10
180
3900
10
200
3900
10
220
4700
10
240
5600
10

Minimum Command Trigger Circuit for Impulse Energizing:
* Pull in

** Drop out

*** without
     drop out
Commands for pull in and drop out require the following minimum duration in ms:

Pull in
a
Drop out
b
Max. duration of triggering without drop out
c
25-30
25-30
8 VA / 2.5 W

Change-over Time:
De-energizing of contactor A causes energizing of contactor B (control switch).

* Signal TA     ** main contacts A     *** main contacts B
Commands for pull in and drop out require the following minimum duration in ms:
Response time in ms
a
b
20-30
10-17