MULTIPOLE RELAY Type S1500

Code No
(Points [.] are placeholders for individual digits. See footnote for details.)
Contacts
Distinct. No
 
NO
NC
EN 50111
8
-
80E
View dimensional drawing
7
1
71E
View dimensional drawing
6
2
62E
View dimensional drawing
5
3
53E
View dimensional drawing
4
4
44E
View dimensional drawing
3
5
-
View dimensional drawing
2
6
-
View dimensional drawing
7
0
-
View dimensional drawing
6
1
-
View dimensional drawing
5
2
-
View dimensional drawing
4
3
-
View dimensional drawing
6
-
60E
View dimensional drawing
5
1
51E
View dimensional drawing
4
2
42E
View dimensional drawing
5
-
50E
View dimensional drawing
4
1
41E
View dimensional drawing

.... depends on the coil frequency and voltage. Click here to view coil types

1) These multipole relays can be equipped with 1 auxiliary contact delayed opening. To order such a multipole relay the code-number has to be supplemented by - 001. For example: S1500 A220/0071- 001

Coil Characteristics:

Technical data:
Insulation Voltage Ui:
690V (600 V UL/CSA)
 
Valid for lines with grounded common neutral termination, overload category III, pollution degree 3. Values for other supply systems on request.
 
Thermal Current Iu/Ith open:
16 A
Ithe enclosed:
10 A
 
Ampere-Rating UL, CSA:
16 amp. / 600 VAC
 
Pilot Duty UL, CSA
Rating Code A600 (Heavy Duty)
 
Max. Fuse Size (gL-charac.):
16 A
 
Mechanical Life Expectancy:
 
AC powered
30 x 106 No. of operations
DC powered
6 x 106 No. of operations
 
Wire Gage:
 
single-core wire
0.75-4 mm2 / AWG 18-12
flexible wire with sleeve
0.5-2.5 mm2 / AWG 20-14

Operational Current Ie [A]:
 
240 V
380-440 V
500 V
AC-15
6
5
2.5

Operational Current Ie [A] / DC-13:
 
24 V
60 V
110 V
220 V
L/R <= 15 ms
1 contact
16
6
2
0.5
2 in series
-
16
8
2
3 in series
-
-
16
4.5
L/R <= 50 ms
1 contact
16
2.4
0.7
0.2
2 in series
-
10
3
0.7
3 in series
-
16
7
1.6
L/R <= 200 ms
1 contact
0.7
0.12
0.01
-
2 in series
2
0.4
0.12
0.01
3 in series
4
0.8
0.3
0.07
Show Guide & Help