MULTIPOLE RELAY Type S1200

Code No
(Points [.] are placeholders for individual digits. See footnote for details.)
Contacts
Distinct. No
 
NO
NC
EN 50111
4
-
40E
View dimensional drawing
3
1
31E
View dimensional drawing
2
2
22E
View dimensional drawing
1
3
13E
View dimensional drawing
-
4
04E
View dimensional drawing
3
-
30E
View dimensional drawing
2
1
21E
View dimensional drawing
1
2
12E
View dimensional drawing
2
0
20E
View dimensional drawing
1
1
11E
View dimensional drawing
1
0
10E
View dimensional drawing
-
1
01E
View dimensional drawing

.... depends on the coil frequency and voltage. Click here to view coil types

1) These multipole relays can be equipped with 1 auxiliary contact delayed opening. To order such a multipole relay the code-number has to be supplemented by - 001. For example: S1200 A220/0031- 001

Coil Characteristics:

Technical data:
Insulation Voltage Ui:
690V (600 V UL/CSA)
 
Valid for lines with grounded common neutral termination, overload category III, pollution degree 3. Values for other supply systems on request.
 
Thermal Current Iu/Ith open:
20 A
Ithe enclosed:
16 A
 
Ampere-Rating UL, CSA:
20 amp. / 600 VAC
 
Pilot Duty UL, CSA
Rating Code A600 (Heavy Duty)
 
Max. Fuse Size (gL-charac.):
20 A
 
Mechanical Life Expectancy:
 
AC powered
30 x 106 No. of operations
DC powered
6 x 106 No. of operations
 
Wire Gage:
 
single-core wire
0.75-4 mm2 / AWG 18-12
flexible wire with sleeve
0.5-2.5 mm2 / AWG 20-14

Operational Current Ie [A]:
 
240 V
380-440 V
500 V
AC-15
8
6
3

Operational Current Ie [A] / DC-13:
 
24 V
60 V
110 V
220 V
L/R <= 15 ms
1 contact
20
8
2.4
0.6
2 in series
-
20
11
2.4
3 in series
-
-
20
5.5
L/R <= 50 ms
1 contact
20
3
0.9
0.25
2 in series
-
13.5
3.8
0.9
3 in series
-
20
9
2
L/R <= 200 ms
1 contact
0.9
0.15
0.02
0.01
2 in series
2.5
0.5
0.15
0.02
3 in series
5
1
0.35
0.09
Show Guide & Help