CONTACTOR Type R3570 - 2 POLE

Code No
(Points [.] are placeholders for individual digits. See footnote for details.)
Main Contacts
Auxiliary Contacts
 
NO
NC
NO
NC
2
-
-
-
View dimensional drawing
2
-
4
2
View dimensional drawing
2
-
3
3
View dimensional drawing
2
-
2
4
View dimensional drawing

.... depends on the coil frequency and voltage. Click here to view coil types

1) These contactors can be equipped with 1 auxiliary contact delayed opening. To order such a contactor the code-number has to be supplemented by - 001. For example: R3570 A220/2024- 001

Coil Characteristics:

Technical data - Main Contacts:
Insulation Voltage Ui:
690V (600 V UL/CSA)
 
Valid for lines with grounded common neutral termination, overload category III, pollution degree 3. Values for other supply systems on request.
 
Thermal Current Iu/Ith open:
115 A
Ithe enclosed:
100 A
 
Ampere-Rating UL, CSA:
100 amp. / 600 VAC
 
Max. Fuse Size (gL-charac.)
Assignment "1" + "2":

125 A
 
Mechanical Life Expectancy:
 
AC powered
20 x 106 No. of operations
DC powered
3 x 106 No. of operations
 
Wire Gage:
 
single-core wire
6-35 mm2 / AWG 8-2
flexible wire with sleeve
4-25 mm2 / AWG 10-4

Operational Current/Rating(1 phase):
 
220-240 V
380-440 V
500 V
660-690 V
AC-1 open [A]
115
115
115
115
AC-1 enclosed [A]
100
100
100
100
AC-3 [kW]
7.5
11
15
-
AC-4 [kW]
5.5
7.5
11
-

HP-Rating(single phase):
 
120 V
240 V
480 V
600 V
UL, CSA [HP]
5
10
20
25

Technical data - Auxiliary Contacts:
Insulation Voltage Ui:
690V (600 V UL/CSA)
 
Valid for lines with grounded common neutral termination, overload category III, pollution degree 3. Values for other supply systems on request.
 
Thermal Current Iu/Ith open:
16 A
 
Pilot Duty UL, CSA
Rating Code A600 (Heavy Duty)
 
Max. Fuse Size (gL-charac.):
16A
 
Wire Gage:
 
single-core wire
0.75-4 mm2 / AWG 18-12
flexible wire with sleeve
0.5-2.5 mm2 / AWG 20-14

Operational Current Ie:
 
230 V
400 V
500 V
AC-15 [A]
6
5
2.5
Show Guide & Help